Issue: The CDC2550LX can experience dome drift if the calibration gets off. Very easy repair with button and joystick pushes only. Follow the below procedure to re-calibrate the joystick to stop the drift.
Resolution: HKBD01 KEYBOARD JOYSTICK CALIBRATION
- Turn the power on. If the keyboard is in the scan mode, press ESC key
- Press PIP x 4, ENTER to enter the factory log on mode
- Select the 2. Set Joystick using the joystick
- Press ENTER without moving the joystick.
- Press ENTER after holding and moving the joystick to the right end
- Press ENTER after holding and moving the joystick to the left end.
- Press ENTER after holding and moving the joystick to the up end.
Ver x.xx
Password : 9,9,9,9
System Setup
- Ven : Default
X:xx Y:xx Z:xx
Press Enter!
X:xx Y:xx Z:xx
X:xx Y:xx Z:xx
Right + Enter
RX:xx
left + Enter
LX:xx
UP + Enter
UY:xx
- Press ENTER after holding and moving the joystick to the down end
- Press ENTER after holding and turning the joystick-handle counterclockwise to the
end
- Press ENTER after holding and turning the joystick-handle clockwise to the end
- If fail, press ENTER. Try again from step3.
- If success, it becomes the automatic reboot.
DOWN + Enter
DY:xx
Zoom Right + Enter
RZ:xx
Zoom Right + Enter
RZ:xx
Joystick error!!
Press ENTER key
Joystick OK!!